The ACU10FD-XP is a full-featured flow computer that integrates the functions of a manual operator, display, and integrator. It can input 1-4 flow signals, and users can customize professional software. The flow computer directly receives digital signals, thus surpassing conventional secondary instruments using analog models in terms of accuracy, anti-interference ability, and signal transmission distance.

Overview
Specifications
◆7-inch monochrome backlit STN LCD
◆Can be used with various models of MFC/MFM or PLC (modbus protocol)
◆Multi-channel simultaneous display and single-channel multi-parameter display
◆Has an alarm list function and displays alarm information line by line
◆Software customizable, buttons can be defined as function keys
◆Time-sharing accumulation function and password protection function
The ACU10FD-XP flow computer directly accepts digital signals, thus surpassing conventional analog secondary instruments in accuracy, anti-interference capability, and signal transmission distance.
The ACU10FD-XP is a full-featured flow computer that integrates the functions of a manual operator, display, and integrator. It can input 1-4 flow signals, and users can customize professional software. The large screen display and ultra-thin structure (43mm thickness) make it easy to install on various devices.
| Display | Type | Blue LED | |||
| Lifespan | Over 20000 hours, ambient temperature 45 degrees, 24-hour operation | ||||
| Display Area | 154*87 | ||||
| Brightness | Adjustable | ||||
| Text Setting | Simplified Chinese/English | ||||
| Character Size | Dot matrix font Vector font | ||||
| Buttons | Touch | ||||
| Memory | Screen | 64KB FlashROM | |||
| Data | 1KB SRAM | ||||
| Interface | Download Port | RS232 | |||
| Communication Port | RS485 MODBUS protocol Connection method DB 9-pin | ||||
| Electrical Characteristics | Power Supply | DC22V~DC26V | |||
| External Power Supply | DC24V | ||||
| Power Consumption | <140ma | ||||
| Allowable Power Failure | Less than 10ms (actual power failure less than 1 second) | ||||
| Voltage Surge Resistance | AC 1000 V, 20mA less than 1 minute | ||||
| Insulation Resistance | Over 10M, DC500 F | ||||
| Environment | Operating Temperature | 0~50 degrees | |||
| Storage Temperature | -20~60℃ | ||||
| Operating Humidity | 10%RH to 90%RH (no condensation) | ||||
| Anti-interference Capability | Interference pressure: 1500 V P-P pulse cycle 1uS duration | ||||
| 1 minute | |||||
| Air | No corrosive gases | ||||
| Cooling Method | Natural air cooling | ||||
| Structure | External Dimensions | 202*147*42.5mm | |||
| Panel Opening Dimensions | 192*138mm | ||||